Operational Characteristics: CME256
Cycle Times (minutes):
System Pressures (PSIG):
A - E Series Refrigerant Charge, R-404A
•
Air cooled: 24 ounces
•
Water cooled: 14 ounces
F Series Refrigerant Charge, R-404A
•
Air Cooled: 24 ounces
•
Water Cooled: 13 ounces
Typical Compressor Amps
•
Freeze:7-9
•
Harvest: 8
Typical Harvest Ice Weight
•
3.25 to 3.5 lb.
Water Cooled:
•
Discharge Pressure: 245 PSIG
•
Hi Pressure Cuts Out at: 450 PSIG
Fan Control Switch - for units so equipped:
•
CutIn:240PSIG+-20PSIG
•
Cut Out: 190 PSIG+-10PSIG
CME256, 506, 656, 806: AutoIQ™ Cubers
July 2002
Page 27
Air Cooled 70
o
F. indoor air, 50
o
F. water 90
o
F. indoor air, 70
o
F. water
Freeze 15 - 17 17 - 19
Harvest 1.5 - 2 1:30 - 2
Water Cooled 70
o
F. indoor air, 50
o
F. water 90
o
F. indoor air, 70
o
F. water
Freeze 13 - 15 17 - 19
Harvest 1:30 - 2 1:45 - 2:15
Air Cooled 70
o
F. indoor air, 50
o
F. water 90
o
F. indoor air, 70
o
F. water
Suction: End of Freeze 25 - 27 28 - 30
Suction: Peak in Harvest 95 - 105 95 - 110
Discharge: 5 minutes into Freeze 240 - 250 250 - 265
Discharge: Minimum in Harvest 165 - 185 175 - 195
Water Cooled 70
o
F. indoor air, 50
o
F. water 90
o
F. indoor air, 70
o
F. water
Suction: End of Freeze 24 - 26 26 - 28
Suction: Peak in Harvest 80 - 90 95 - 105
Discharge: 245 PSIG 245 PSIG
Discharge: Minimum in Harvest 125 - 135 145 - 155